JMB/JMC

flow meter controller

JMA

Tank with valves

Flow Sensor

JMA

Tank with valves

Flow Sensor

JMA

Tank with valves

Flow Sensor

JMA

Tank with valves

 

 

 

JMA

Tank with valves

Note: JMB is a single sensor controller with maximum 5 signal outputs

      JMC is a 3 sensors controller with maximum 3 signal outputs

 

   JM system is combined by a stager and a time/volume controller. The stager is a rotary pilot valve with multiple ports through which control fluid is directed, thereby operating diaphragm valves installed in a process system. The stagers are constructed of durable, non-corroding, self-lubricating material, maintenance free life. 

  All valves are high quality hydraulic or pneumatic diaphragm valves which is widely used in the world. 1.5’-6’ valves and diameter 600~3000mm tanks are all compatible to JM system.

  • JMA stager controller functions:

     Password setting

     Calendar

     Regeneration stage and regeneration time indication

     JMA can be initiated manually or through remote control. Timer initiation and interval initiation are also available.

     Manual step by step initiation (only for system commissioning)

     Reset function

     Stages (1-8) and stage duration (5-9999 Sec) settings

     System working stage indication (Service or regeneration stage indication)

     Data protection after power cut: settings and data can be stored for 3 years.

     Waterproof and rotproof enclosure

  • Stager working principle:

The stager may be manually operated or driven by an electric motor that operated through an adjustable timer or flowmeter program. The stager functions by opening and closing its ports, singly or in combination, in a sequence that fit the need of the system. The “positions” in the sequence correspond to the number of “stager” in the process (See chart 1). The port that are opened allow the pressurized fluid to flow to and operate some diaphragm valves, while venting other valves—allowing them to return to their normal positions.  

The stagers can use either hydraulic or pneumatic control fluid. Continuous electrical power is not required to maintain the positions of the valves such as in a solenoid operated system. Greatly avoid the system breakdown because of power failure.  

All types of complex application can be controlled by stager controller system through correct design and combination of the stagers.

 

   Next is Typical Circuit Application for JMA 502

STAGER POSITION

SOFTENER FUNCTION

VALVES OPEN

4

SERVICE

1, 2

1

BACKWASH

3, 4 (2A)

2

BRINE

5, 2  (2A)

3

FAST RINSE

6, 1  (2A)

  • JMA stager controller specifications:

         Automatic restoration function

         Waterproof enclosure (waterproof and shockproof)

         Power supply: 220VAC/50HZ

         Timer initiation setting: any time of the day 7 days one week

         8 stages available with duration from 5 to 9999 seconds for each stage

         Manually initiation

         Service/regeneration Light indication

         Auxiliary signal output

    • Technical figures:

    Electrical supply: 220VAC/50HZ, 10W

  • Remote control signal: At least 2 seconds/dry contactor

  • Pressure port size: 1/8”G thread

  • Control fluid:  hydraulic or pneumatic (100μfilter is recommended for the system)

  • Control fluid pressure: 0.2~0.8MPa

  • Temperature: 4~60

  • Enclosure size: 270 mm X 170 mm X 105 mm                                       BACK TO TOP

    Applications:

    Item ID

    Typical application

    Stage program

    JMA 501

    Filter

    Service→backwash→rinse

    JMA 502

    Co-current regeneration softener

    Service→backwash→brine + slow wash→rinse

    JMA 503

    Filter

    service→backwash

    JMA 505

    Counter-current regeneration softener

    Service→backwash→brine + slow wash→rinse

    JMA 506

    3 tanks filter

    service→1#backwash→2#backwash→3#backwash

    JMA 507

    4 tanks filter

    service→1#backwash→→→4#backwash

    JMA 508

    5 tanks filter

    service→1#backwash→→→→5#backwash

    JMA 523

    2 tanks filter (1service 1 stand by )

    1#service→1#backwsh→2#service→2#backwash

    JMA 524

    Co-current regeneration water softener 

    service→backwash→brine→slow wash→rinse→refill

    JMA 525

    Co-current regeneration water softener

    service→backwash→brine→slow wash→rinse

    JMA 526

    Co-current regeneration water softener

    service→backwash→brine→rinse→refill

    JMA 527

    2 tanks parallel filter

    service→backwash 1→rinse 1→backwash 2→rinse 2

    JMA 528

    Filter

    service→drain→air flush→backwash→rinse

    JMA 529

    Brine recycle water softener

    service→backwash→brine→brine+slow wash→brine recycle →rinse

    JMA 530

    6 tanks filter

    service→1#backwash→→→→6#backwash

    JMA 531

    7tanks filter

    service→1#backwash→→→→7#backwash

  • JMB/C volume controller                                                                         BACK TO TOP

JMB/C volume controller is a new product developed on the basis of advanced CMOS chip technology. It is widely used in filtration system, water soft system, and desalination systems. JMB/C has many functions such as volume display, remain volume display, regeneration program presetting, system working stage display, signal feedback, solenoid signal output.

  • JMB/C functions:

◆     Password setting

◆     JMB: single flow sensor signal input controller

        JMC:1 to 3 flow sensor signal input controller

◆     K value setting (For K value setting please check K value list)

◆     Flow rate display (0-999t/h); remaining volume display(1-9999.9t)

◆     Total volume display and data clearance function

◆     Stages display (service, regeneration, stand by, feedback )

◆     Manual regeneration

◆     Regeneration initiation signal duration setting(2-9999 sec)

◆     Working modes:

           JMC: C1, D2, D3, E2, E3

           JMB: C1, C2, C3, C4. C5, D2, D3, D4, D5

Note: C: service simultaneously and regeneration one by one.

     D: all in service while one in stand by

     E: service simultaneously and regeneration separately

◆     Auxiliary signal output of regeneration

◆     Power cut data protection: settings and data can be stored for 3 years.

◆     Waterproof and rotproof enclosure

  • Specification

◆     Volume sensor pulse input: 0-10 K; 4-12V

◆     Sample cycle: 0.2 second

◆     Output: AC220/2A

◆     Feed back: dry contact

◆     LCD display

◆     Power: 100-265V/AC; 5W

◆     Temperature: 4-60℃

◆     Humidity: ≤84%RH

◆     Enclosure size: 260X170X105mm

                                                           BACK TO TOP

 